Operating the Drive 4-3
650V AC Drive
Set-up as an Open-loop Drive (V/F Fluxing)
The parameters most likely to require attention in this (default) control mode (VOLTS / HZ) are
shown below.
Product Code
Set the speed in Hz at which the 650V will
run when the maximum setpoint is
The time taken for the 650V output
frequency to ramp up from zero to MAX
DECEL TIME 10.0 s The time taken for the 650V output
frequency to ramp down from MAX
Product Code
Enter the motor nameplate full-load line
current
BASE FREQUENCY Default is
Product Code
Enter the output frequency from the motor
nameplate
JOG SETPOINT 10.0 % Drive speed setpoint whilst jogging
RUN STOP MODE 0 Selects a type of "ramp to standstill", for
when RUN signal is removed
Constant torque V to F characteristic
Selects between Heavy or Normal mode
of operation
Product Code
Enter a boost for starting torque to help
with high friction loads
CONTROL MODE
VOLTS / HZ
(0)
This parameter contains the main method
of motor control used by the drive, and
by default is set to VOLTS/HZ
Additional parameters for when parameters
CL
04 (SLIP COMP ENABLE) and/or
CL
05
(STABILISATION ENABLE) are enabled:
This parameter contains the motor
nameplate full-load rated speed. This is
the motor speed in rpm at ba
se frequency
minus full load slip
MOTOR POLES 4 pole This parameter contains the motor
Product Code
This parameter contains the motor
nameplate voltage at base frequency
Product Code
This parameter contains the motor model
no-load line current as determined by the