Technical Specifications 9-9
650V AC Drive
Electrical Ratings (400V Build Variant)
Power Supply = 380-460V ±10%, 50/60Hz
±
5%
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Model Number
(Europe)
Catalog Number
(North America)
Motor
Power
Output
Current
(A)
Input
Current
(A)
Heatsink
Power
Loss (W)
Total
Power
Loss
(W)
Maximum
Switching
Frequency
(kHz)
Input
Bridge I
2
t
(A
2
s)
FRAME E :
Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac
input. Prospective short circuit current 18kA.
* For UL Listed products rated at 30kW/40Hp, a supply voltage of 460V is required. The higher
current ratings are applicable to non UL applications only.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650V-432590E 30kW 59 68 590 690 3 15000
650V/0040/460/.. 40Hp 59 57 590 690 3 15000
650V-432730E 37kW 73 81 730 850 3 18000
650V/0050/460/.. 50Hp 73 68 730 850 3 18000
650V-432780E 45kW 87 95 880 880 3 18000
650V/0060/460/.. 60Hp 87 80 880 880 3 18000
Normal Duty
(Output Overload Motoring 110% for 30s)
650V-432590E 37kW 73 81 733 848 3 15000
650V/0040/460/.. 50Hp 73 68 733 848 3 15000
650V-432730E 45kW 87 95 901 1029 3 18000
650V/0050/460/.. 60Hp 87 80 901 1029 3 18000
650V-432780E 55kW 105 110 1094 1242 3 18000
650V/0060/460/.. 75Hp 105 95 1094 1242 3 18000
FRAME F :
Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac
input. Prospective short circuit current 18kA.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650V-433105F 55kW 105 114 920 1220 3 100,000
650V/0075/460/.. 75Hp 100 99 900 1130 3 100,000
650V-433145F 75kW 145 143 1320 1670 3 100,000
650V/0100/460/.. 100Hp 130 124 1200 1500 3 100,000
650V-433156F 90kW 180 164 1490 1950 3 100,000
650V/0125/460/.. 125Hp 156 148 1340 1780 3 100,000
650V-433180F 90kW 180 164 1490 1950 3 100,000
650V/0150/460/.. 150Hp 180 169 1670 2180 3 100,000
Normal Duty
(Output Overload Motoring 110% for 30s)
650V-433105F 75kW 145 143 1400 1670 3 100,000
650V/0075/460/.. 100Hp 125 124 1200 1500 3 100,000
650V-433145F 90kW 165 164 1580 1950 3 100,000
650V/0100/460/.. 125Hp 156 148 1340 1780 3 100,000
650V-433156F 110kW 205 195 1800 1950 3 100,000
650V/0125/460/.. 150Hp 180 169 1670 2180 3 100,000
650V-433180F 110kW 205 195 1800 1950 3 100,000
650V/0150/460/.. 150Hp 180 169 1670 2180 3 100,000

Table of Contents