Technical Specifications 9-19 
650V AC Drive 
Supply Harmonic Analysis (Frame E Normal Duty) 
Assumptions: 10000A short circuit supply capability, 
equivalent to 73µH supply impedance at 400V where Q
1n 
 is the 
rated rms value of the fundamental voltage of the supply 
transformer. The results conform to stage 1, stage 2 and stage 
3 of the Engineering Recommendation G.5/3 September 1976, 
Classification ‘C’: Limits for Harmonics in the UK Electricity 
 
Voltage (V) 
230  400  500 
Motor Power 
22.0  30.0  37.0  45.0  30.0  37.0  45.0 
Typical 
Motor 
Efficiency % 
90  90  90  90  90  90  90 
No. 
RMS Current (A) 
102.1  64.3  74.8  89.1  51.5  63.6  75.5 
0.1  0.1  0.1  0.1  0.1  0.0  0.0 
49.1  41.9  48.7  55.2  35.4  43.1  48.9 
21.7  26.0  30.3  32.2  23.3  28.0  30.1 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
6.3  4.4  5.0  5.1  5.1  5.7  5.4 
4.1  4.0  4.6  5.9  3.3  4.1  5.1 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
2.8  2.3  2.7  2.5  2.6  3.0  2.8 
1.7  1.6  1.8  2.3  1.5  1.8  2.0 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
1.6  1.4  1.6  1.5  1.4  1.6  1.6 
1.0  0.9  1.1  1.2  1.0  1.2  1.1 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
1.0  0.8  1.0  1.0  0.7  0.9  1.0 
0.7  0.6  0.7  0.8  0.7  0.8  0.7 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.7  0.5  0.6  0.7  0.4  0.6  0.6 
0.5  0.5  0.5  0.6  0.4  0.6  0.5 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.5  0.4  0.4  0.5  0.3  0.4  0.4 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.4  0.3  0.4  0.4  0.3  0.4  0.4 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.3  0.2  0.3  0.3  0.2  0.3  0.3 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
0.3  0.2  0.3  0.4  0.2  0.3  0.3 
0.0  0.0  0.0  0.0  0.0  0.0  0.0 
Total RMS 
115.6  81.3  94.6  110.0  67.1  82.2  95.2 
1.84  2.98  3.46  3.84  1.52  1.84  1.02