6-2  Programming Your Application
 
650V AC Drive 
MMI Parameters Table 
 
APPLICATION  This parameter selects and loads the Application to 
be used. APP 0 will not control a motor. APP 6, 7 & 
8 are for future use. You can edit an Application in 
DSE and then set this parameter to CUSTOM to 
produce your own custom Application. 
Refer to the 650V Software Product Manual, 
Chapter 5: "Applications" which gives detailed 
information about each Application.  
Note:
 
Parameter values are changed to 
factory settings by loading a new 
Application, except Motor Parameters 
(indicated 
M
) 
0= NULL 
1= STANDARD 
2= LOCAL/REM 
 (AUTO/MANUAL) 
3= PRESETS 
4= RAISE/LOWER 
5= PID 
6= APP 6 
7= APP 7 
8= APP 8 
9= CUSTOM 
1 
 
MAX SPEED 
M 
The frequency at which the 650V will run when 
maximum setpoint is applied. The default is 
Product Code dependent 
7.5 to 300Hz  50 or 
60Hz 
 
MIN SPEED  The minimum frequency at which the 650V will 
run, as a percentage of the MAX SPEED parameter 
-100.0 to 100.0%  0.0% 
 
ACCEL TIME  The time taken for the 650V output frequency to 
ramp up from zero to MAX SPEED 
0.0 to 3000.0s  10.0s 
 
DECEL TIME  The time taken for the 650V output frequency to 
ramp down from MAX SPEED to zero 
0.0 to 3000.0s  10.0s 
 
MOTOR 
CURRENT 
M 
This parameter contains the motor nameplate full-
load line current 
0.01 to 999.99A  product 
code 
dependent 
 
BASE 
FREQUENCY 
M 
The output frequency at which maximum voltage is 
reached. The default is Product Code dependent 
7.5 to 240Hz  50 or 
60Hz 
 
JOG SETPOINT  Speed the 650V will run at if the Jog input is high, 
as a percentage of the MAX SPEED parameter 
-100.0 to 100.0%  10.0% 
 
RUN STOP MODE  RAMPED : The motor speed is reduced to zero at a 
rate set by DECEL TIME (
P
5).  A 2 second DC pulse 
is applied at end of ramp 
COAST : The motor is allowed to freewheel to a 
standstill 
DC INJECTION : On a stop command, the motor 
volts are rapidly reduced at constant frequency to 
deflux the motor. A low frequency braking current 
is then applied until the motor speed is almost 
zero. This is followed by a timed DC pulse to hold 
the motor shaft. 
0=RAMPED 
1=COAST 
2=DC INJECTION 
0 
 
V/F SHAPE  LINEAR LAW: This gives a constant flux 
characteristic up to the BASE FREQUENCY 
FAN LAW: This gives a quadratic flux characteristic 
up to the BASE FREQUENCY. This matches the 
load requirement for fan and most pump 
applications 
Refer to 
P
12 
LINEAR
FREQUENCY
 = BASE FREQUENCY
100%
CONSTANT
POWER RANG
OUTPUT VOLTS
f
B
f
B
QUADRATIC LAW
0=LINEAR LAW 
1=FAN LAW 
0