Programming Your Application 6-3
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
NORMAL DUTY
TIME (s)
150%
% OF RATED MOTOR CURRENT
30
60
100% overload for 30s (Heavy Duty)
127.5%
105%
100%
FALSE - HEAVY DUTY: Inverse time allows 150%
overload for 30s, then ramps back the current limit
to 105% over a 10s period. At a lower load, the
overload area remains the same, e.g. at 127.5%
load for 60s - after 60s has expired, the output of
the inverse time function is ramped back over a
10s period from 150% as before.
TRUE - NORMAL DUTY: current limit is set to
110% motor current, inverse time delay is set to
30s
When
P
11 is changed from FAN LAW to LINEAR
LAW,
P
12 is set to 0 (HEAVY DUTY)
When
P
11 is changed from LINEAR LAW to FAN
LAW,
P
12 is set to 1 (NORMAL DUTY)
P
12 can be changed independently
0=FALSE
1=TRUE
0
FIXED BOOST
M VF
Used to correctly flux the motor at low speeds. This
allows the drive to produce greater starting torque
for high friction loads. It increases the motor volts
above the selected V/F characteristic at the lower
end of the speed range
OUTPUT VOLTS
FREQUENCY
f
B
25%
100%
BOOST
f
B
= BASE FREQUENCY
0%
INCREASING
INCREASED
TORQUE
CONSTANT
POWER RANGE
FLUXING
NORMAL FLUXING
0.00 to 25.00% product
code
dependent
PASSWORD A password may be set to prohibit unauthorised
adjustment of parameters. When
P
99 is set to
non-zero you will be required to match this value
before parameters can be adjusted
0000 – FFFF 0000
Parameters
P
301 to
P
308 are visible in the PAR menu when Application 3 is selected in parameter
P
1
PRESET 0 A user-adjustable speed preset, set by
potentiometer
-100.00 to 100.00 -
PRESET 1 A user-adjustable speed preset -100.00 to 100.00 20.00
PRESET 2 A user-adjustable speed preset -100.00 to 100.00 50.00
PRESET 3 A user-adjustable speed preset -100.00 to 100.00 100.00
PRESET 4 A user-adjustable speed preset -100.00 to 100.00 -10.00
PRESET 5 A user-adjustable speed preset -100.00 to 100.00 -20.00
PRESET 6 A user-adjustable speed preset -100.00 to 100.00 -50.00
PRESET 7 A user-adjustable speed preset -100.00 to 100.00 -100.00
Parameters
P
401 to
P
404 are visible in the PAR menu when Application 4 is selected in parameter
P
1
R/L RAMP TIME The time taken to ramp the Raise/Lower output
from 0.00% to 100.00% of its value
0.0 to 600.0s 10.0s
R/L MAX VALUE The maximum value for the ramp output -100.00 to 100.00% 100.00%
R/L MIN VALUE The minimum value for the ramp output -100.00 to 100.00% 0.00%
NORMAL DUTY was
previously referred to
as Quadratic Torque
in past Drives'
manuals.