EasyManua.ls Logo

Parker 650V series - Hexadecimal Representation of Trips

Parker 650V series
135 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trips and Fault Finding
7-6
650V AC Drive
S
ST24 : AUTO RESTART TRIGGERS+
ID
Trip Name
(MMI 6901)
Trip Name
(MMI 6511 & 6521)
Mask +
User
Disable
41
MAX RPM DATA ERR
ATN8
0x8000
N/A
42
LEAKGE L TIMEOUT
ATN9
0x8000
N/A
43 MOTOR TURNING
ERR
ATNA 0x8000 N/A
44
MOTOR STALL ERR
ATNB
0x8000
N/A
Keypads (MMIs):
Trips shown as MMI displays in the tables above, i.e. , can be disabled using the
keypads in the TRIPS menu. Other trips, as indicated, can be disabled over the Comms.
6901 6511 6521 6911
Hexadecimal Representation of Trips
When more than one trip is to be represented at the same time then
the trip codes are simply added together to form the value displayed.
Within each digit, values between 10 and 15 are displayed as letters
A to F
For example referring to the tables above, if the AUTO RESTART
TRIGGERS parameter is set to 03A0, then this represents:
a “3” in digit 3
an “8” and a “2” in digit 2
(8+2 = 10, displayed as A)
an “0” in digit 1
This in turn represents the trips BRAKE RESISTOR, ANIN FAULT, MOTOR STALLED and
INVERSE TIME.
In the same way, the AUTO RESTART TRIGGERS+ parameter set to 03A0 would represent
BRAKE SHORT CCT, ANIN FAULT, DESAT OVER I
and 10V FAULT.
Fault Finding
Problem
Possible Cause
Remedy
Drive will not power-up Fuse blown Check supply details, fit correct fuse.
Check Product Code against Model No.
Faulty cabling Check all connections are correct/secure.
Check cable continuity
Drive fuse keeps blowing Faulty cabling or connections
wrong
Check for problem and rectify before
replacing with correct fuse
Faulty drive Contact Parker
Cannot obtain power-on state Incorrect or no supply available Check supply details
Motor will not run at switch-on Motor jammed Stop the drive and clear the jam
Motor runs and stops Motor becomes jammed Stop the drive and clear the jam
Open circuit speed reference
potentiometer
Check terminal
Decimal
number
Display
10
A
11
B
12
C
13
D
14
E
15
F

Table of Contents

Other manuals for Parker 650V series