Technical Specifications 9-7
650V AC Drive
Electrical Ratings (230V Build Variant)
Power Supply = 220-240V ±10%, 45-60Hz
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Operation at 208V
±
10% (Frames C, D, E & F)
Nominal motor powers are reduced by 10% when operated at 208V ±10%. Output currents
remain unchanged.
Model Number
(Europe)
Catalog Number
(North America)
Motor
Power
Output
Current
(A)
Input
Current
(A)
Heatsink
Power
Loss
(W)
Total
Power
Loss
(W)
Maximum
Switching
Frequency
(kHz)
Input
Bridge I
2
t
(A
2
s)
FRAME F :
Input currents for kW ratings are at 230V 50Hz ac input. Prospective short circuit current 18kA.
Heavy Duty (Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650V-233104F 30kW 104 102 850 1100 3 100000
650V/0040/230/.. 40Hp 104 102 850 1100 3 100000
650V-233130F 37kW 130 126 1100 1450 3 100000
650V/0050/230/.. 50Hp 130 126 1100 1450 3 100000
650V-233154F 45kW 154 148 1200 1650 3 100000
650V/0060/230/.. 60Hp 154 148 1200 1650 3 100000
Normal Duty (Output Overload Motoring 110% for 30s, 125% for 0.5s short term rating)
650V-233104F 37kW 130 126 1150 1500 3 100000
650V/0040/230/.. 50Hp 130 126 1150 1500 3 100000
650V-233130F 45kW 154 148 1350 1800 3 100000
650V/0050/230/.. 60Hp 154 148 1350 1800 3 100000
650V-233154F 55kW 192 184 1600 2100 3 100000
650V/0060/230/.. 75Hp 192 184 1600 2100 3 100000
Electrical Ratings (400V Build Variant)
Power Supply = 380-460V ±10%, 50/60Hz
±
5%
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Model Number
(Europe)
Catalog Number
(North America)
Motor
Power
Output
Current
(A)
Input
Current
(A)
Heatsink
Power
Loss (W)
Total
Power
Loss
(W)
Maximum
Switching
Frequency
(kHz)
Input
Bridge I
2
t
(A
2
s)
FRAME C :
Input currents for kW ratings are at 400V 50Hz ac input, and for Hp ratings at 460V 60Hz ac
input. Prospective short circuit current 10kA.
* For UL Listed products rated at 15kW/20Hp, a supply voltage of 460V is required. The higher
current ratings are applicable to non UL applications only.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180 % for 0.5s short term rating)
650V-432160C 7.5kW 16 19 240 290 3 4000
650V/0010/460/.. 10Hp 14 16 225 275 3 4000
650V-432230C 11kW 23 26.1 280 330 3 4000
650V/0015/460/.. 15Hp 21 22.1 260 310 3 4000
650V-432300C 15kW 30 37 440 500 3 6000
650V/0020C/460/.. 20Hp 27 31.2 410 470 3 6000