Installing the Drive 3-3
650V AC Drive
Through-Panel Mount Product/Application (Frame C)
(Europe: IP2x, USA/Canada: Open Type).
The drive, without the top cover fitted, can be mounted in a suitable cubicle.
J
Control
Heat
Sink
K
L
M
FORCED AIR FLOW
panel
N
P
Figure Chapter 3 -4 Air Clearance for a Through-Panel Mount Product/Application
Model Recognition
Clearances for Through-Panel Mount
Standard Product (mm)
Through-Panel
Dimensions
J
K
L
M
N
P
Frame C 20 15 70 70
Through-Panel Mount
Bracket Assembly (Frame C)
The through-panel kit is available as a separate
item, part number LA465034U003.
Through-panel mounting a drive in a cubicle
allows you to use a smaller cubicle because
much of the heat generated by the drive is
dissipated outside the cubicle.
Cut the panel aperture to the dimensions
given in the drawing at the end of this
chapter.
Screw the top and bottom brackets to the
drive as shown, torque to 3Nm. When in
position, these complete a mating face for the
panel around the drive.
Fit the top and bottom self-adhesive gasket
material to the brackets making sure that the
gasket covers the gap between the bracket
and heatsink along the top and bottom edge
of the drive.
Fit a gasket to each side of the drive to
complete the gasket seal. Ensure a complete
seal is made; 2 extra side gaskets are
provided.
Offer up the drive to the panel and secure.
Refer to Through-Panel Cutout Details,
page 3-9.