Installing the Drive 3-7
650V AC Drive
Through-Panel Mount Product/Application (Frame E)
(Europe: IP2x, USA/Canada: Open Type).
The drive, without the top cover fitted, can be through-panel mounted in a suitable cubicle.
J
K
L
M
panel
ISOLATED FORCED AIR FLOWS
P
N
Figure Chapter 3 -10 Air Clearance for a Through-Panel Mount Product/Application
Clearances for Through-Panel Mount
Standard Product (mm)
Frame E 0 (zero) 25 70 70 180 129 (panel thickness
not included, max.
thickness 5mm
Through-Panel Mount Bracket
Assembly (Frame E)
The through-panel kit is available as a
separate item, part number LA465058U003.
Through-panel mounting a drive in a cubicle
allows you to use a smaller cubicle because
much of the heat generated by the drive is
dissipated outside the cubicle.
• Cut the panel aperture to the dimensions
given in the drawing at the end of this
chapter.
• Lay the drive on its back.
• Lightly screw the top and bottom brackets
to the drive as shown.
• Fit the two side brackets to complete the
frame and tighten all screws securely.
• Fit the self-adhesive gasket material to the
mating face of the drive to produce an air-
tight seal between the drive and the panel.
• Offer up the drive to the panel and secure.
Refer to Through-Panel Cutout Details,
page 3-8.