EasyManua.ls Logo

Parker 650V series - Supply Short Circuit Rating

Parker 650V series
135 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-16 Programming Your Application
650V AC Drive
Skip Frequencies
Parameters
S
ST11 to
S
ST14 control two programmable skip frequencies that can prevent the
drive from operating at frequencies that cause mechanical resonance in the load.
Enter the value of the frequency that causes the resonance into the SKIP FREQUENCY
parameter.
Enter a width for the skip band into the SKIP FREQUENCY BAND parameter.
The drive will then avoid sustained operation within the forbidden band as shown in the
diagram. The skip frequencies are symmetrical and thus work in forward and reverse.
Setting SKIP FREQUENCY or SKIP FREQUENCY BAND to 0 disables the corresponding
band.
Skip band
Skip Frequency
Setpoint
Drive
Frequency
Setpoint
Drive
Frequency
Frequency 1
Frequency 2
Setpoint
Drive
Frequency
Frequency 1
Frequency 2

Table of Contents

Other manuals for Parker 650V series

Related product manuals