Programming Your Application 6-23
650V AC Drive
460V Build Power Dependent Defaults (US)
POWER MOTOR DATA 1158
55.00 kw 75.00 kw 90.00 kw 90.00 kw
MOTOR CURRENT MOTOR DATA 64
97.00 A 130.00 A 151.00 A 151.00 A
MAG CURRENT MOTOR DATA 65
29.10 A 39.60 A 45.30 A 45.30 A
NAMEPLATE RPM MOTOR DATA 83
1750.0 RPM 1750.0 RPM 1750.0 RPM 1750.0 RPM
MOTOR VOLTAGE MOTOR DATA 1160
460.0 V 460.0 V 460.0 V 460.0 V
POWER FACTOR MOTOR DATA 242
0.86 0.87 0.9 0.9
STATOR RES MOTOR DATA 119
0.1587 ohms 0.1166 ohms 0.1020 ohms 0.1020 ohms
LEAKAGE INDUC MOTOR DATA 120
5.05 mH 3.71 mH 3.25 mH 3.25 mH
MUTUAL INDUC MOTOR DATA 121
20.21 mH 14.85 mH 12.98 mH 12.98 mH
ROTOR TIME
CONST
MOTOR DATA 1163
607.30 ms 607.30 ms 759.12 ms 759.12 ms
BRAKE POWER DYNAMIC
BRAKING
78
0.1 kw 0.1 kw 0.1 kw 0.1 kw
FREQUENCY INJ BRAKING 577
6.0 Hz 6.0 Hz 6.0 Hz 6.0 Hz
DEFLUX TIME INJ BRAKING 710
2.0 s 2.0 s 2.0 s 2.0 s
BASE VOLTS INJ BRAKING 739
75.00% 75.00% 75.00% 75.00%
DC LEVEL INJ BRAKING 581
1.30% 1.30% 1.30% 1.30%
DC PULSE INJ BRAKING 579
2.0 s 2.0 s 2.0 s 2.0 s
FINAL DC PULSE INJ BRAKING 580
3.0 s 3.0 s 3.0 s 3.0 s
FIXED BOOST FLUXING 107
0.00% 0.00% 0.00% 0.00%
ACCEL TIME REFERENCE
RAMP
258
30.0 s 30.0 s 30.0 s 30.0 s
DECEL TIME REFERENCE
RAMP
259
30.0 s 30.0 s 30.0 s 30.0 s
DEFLUX DELAY PATTERN GEN 100
4.0 s 4.0 s 4.0 s 4.0 s
SEARCH VOLTS FLYCATCHING 573
8.00% 8.00% 8.00% 8.00%
SEARCH BOOST FLYCATCHING 32
15.00% 15.00% 15.00% 15.00%
SEARCH TIME FLYCATCHING 574
15.0 s 15.0 s 15.0 s 15.0 s
REFLUX TIME FLYCATCHING 709
6.0 s 6.0 s 6.0 s 6.0 s
OVERLOAD MOTOR DATA 1164
2.2 2.2 2.2 2.2
SPEED PROP GAIN SPEED LOOP 1187
20.00 20.00 20.00 20.00
SPEED INT TIME SPEED LOOP 1188
100 ms 100 ms 100 ms 100 ms
MOTOR
CONNECTION
MOTOR DATA 124
1 : STAR 1 : STAR 1 : STAR 1 : STAR
BRAKE
RESISTANCE
DYNAMIC
BRAKING
77
100 100 100 100
BOOST MODE FLUXING 1058
0 0 0 0