Function
Code
Function Denition Setting Range Mfr’s Value Change
F608 Stall Current Level (%) 60-200 160
F609 Stall Voltage Level (%) 110-200
1 phase: 130
3 phase: 140
F610 Stall Protection Time 0.1-3000 60.0
F611
Dynamic Braking
Threshold (V)
200~1000
Subject
to inverter
model
D
F612
Dynamic Braking Duty
Ratio (%)
0-100 80 X
F613 Flycatching
0: Invalid
1: Valid
2: Valid at rst time
0 X
F614 Flycatching Rate Mode
0: Flycatching from
frequency memory
1: Flycatching from
max frequency
2: Flycatching from
freq memory and
direction memory
3: Flycatching
from max freq and
direction memory
0 X
F615 Flycatching Rate 1-100 20 X
F613-F621
Reserved
F619
Flycatching (fault) Time
out (S)
0-3000 60
F620-F621
Reserved
F622 Dynamic Braking Mode
0: Fixed duty ratio
1: Auto duty ratio
0
F627
Current Limiting when
Flycatching
50-200 100 X
F631
VDC Adjustment
Selection
0: Disabled 1:
Enabled
0
F632
Target voltage of VDC
adjustor (V)
200-800
Subject
to inverter
model
√o
F633-F649
Reserved
F650
High-frequency
performance
Setting range:
0: Invalid 1:
Terminal enabled
2: Enabled mode 1
3: Enabled mode 2
2 Xo
F651 Switchover frequency 1 F652-150.00 100.00 √o
F652 Switchover frequency 2 0-F651 95.00 √o
F653-F670
Reserved
10-13 Parameter List and Default Settings