Function
Code
Function Denition Setting Range Mfr’s Value Change
F711 Trip 1 Fault Frequency
D
F712 Trip 1 Fault Current
D
F713
Trip 1 Fault DC Bus
Voltage
D
F714 Trip 2 Fault Frequency
D
F715 Trip 2 Fault Current
D
F716
Trip 2 Fault DC Bus
Voltage
D
F717 Trip 3 Fault Frequency
D
F718 Trip 3 Fault Current
D
F719
Trip 3 Fault DC Bus
Voltage
D
F720
Number of Overcurrent
Faults
D
F721
Number of Overvoltage
Protection Faults
D
F722
Number of Overheat
Protection Faults
D
F723
Number of Overload
Protection Faults
D
F724 Input Phase Loss 0: Disabled; 1: Enabled 1 oX
F725 Reserved
F726 Overheat 0: Disabled; 1: Enabled 1 oX
F727 Output Phase Loss 0: Disabled; 1: Enabled 0 o
F728
Input Phase Loss Trip
Delay
0.1-60.0 0.5
F730
Overheat Protection
Trip Delay
0.1-60.0 5.0
F732
Under-Voltage
Threshold
0-450
Subject
to inverter
model
o
F737
Over-current 1
Protection
0: Disabled; 1: Enabled 0
F738
Over-current 1
Protection Setpoint
0.50-3.00 2.50
F739
Over-current 1
Protection Record
D
10-15 Parameter List and Default Settings