Function
Code
Function Denition Setting Range Mfr’s Value Change
F740 Reserved
F741
Analog Disconnected
Protection
0: Invalid
1: Stop and AErr
displays.
2: Stop and AErr is not
displayed.
3: Inverter runs at the
min frequency.
4: Reserved.
0 √
F742
Threshold of Analog
Disconnected
Protection (%)
1-100 50 o
F745
Threshold of Pre-alarm
Overheat (%)
0~100 80 o*
F747
Carrier Frequency
Auto-adjusting
0: Invalid 1: Valid 1 √
F754
Zero-current Threshold
(%)
0-200 5 X
F755
Duration time of zero-
current
0-60 0.5 √
Function
Code
Function Denition Setting Range Mfr’s Value Change
F800
Motor’s Parameters
Selection
Setting range:
0: Invalid;
1: Rotating tuning.;
2: Stationary tuning
0 X
F801 Rated Motor Power 0.2-1000kW oX
F802 Rated Motor Voltage 1-440V oX
F803 Rated Motor Current 0.1-6500A oX
F804 Number of Motor Poles 2-100 4 oX
F805 Base Motor RPM 1-30000 oX
F806 Stator Resistance Ω
0.001-65.53Ω (22kw
and below)
0.1~6553mΩ (above
22kw)
Subject
to inverter
model
oX
Parameter List and Default Settings
10-16