If the factory is not notified that a PoolPak is to be curb mounted, the PoolPak base
will not be watertight, it will leak, and it will not be properly insulated.
NOTE
Curb Mounting
Curbs have been designed specifically for the PoolPak® product line. Contact factory for roof curb dimensions. The
outside dimensions of the curb are such that the base of the PoolPak® overhangs the edge of the curb on each side.
This aids in preventing rain water, running down the sides of the unit, from getting between the base of the PoolPak
and the curb.
It is the installing contractor’s responsibility to properly complete the following:
Flash the curb into the roof
Insulate the curb
Connect the supply and return ducts to the PoolPak
Connect condensate drain lines with appropriate traps
Seal the curb top surface to the bottom of the PoolPak with supplied gasket
If specified when ordering, all water piping connections can be made through the curb. These water connections
include:
Pool water
Condensate
Auxiliary hot water coil
Chilled water coil
If the PoolPak is to be mounted on another manufacturer’s curb, the PoolPak factory must be notified of this at the
time the PoolPak sales order is submitted. PoolPak units produced for curb mounting, whether on a PoolPak curb or
on another manufacturer’s curb, receive special weatherizing and insulating that non-curb mounted PoolPak units do