EasyManua.ls Logo

PoolPak MPK series - Unit Configuration

PoolPak MPK series
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2017 PoolPak LLC. All rights reserved. MPK Series - Installation, Operation and Maintenance | 65
PoolPak
®
MPK Series IOM
Figure 5-23. Unit Configuration - Installed Features Menu
The Unit Configuration menu is where to access system set-up parameters. From here, the following configuration
parameters can be accessed: Installed Features, Supply Fan, Exhaust Fan, Purge Fan, Compressor System, Dampers,
Pool Water Heating, Auxiliary Air Heating System, Auxiliary Air Cooling System, Auxiliary Air Dehumidification
System, Space Temperature Control, Space Dewpoint Control, Mixing Box Control, and BAS Interface. For all below
parameters, the default setting is in bold font.
Inst Features – Installed Features
Cpr Stgs Ins – Compressor Stages Installed – 3 (Range 0 to 4)
Cpr1 Wtr Circ – Compressor 1 Water Circuit – A&B (Range A or A&B)
Cpr2 Wtr Circ – Compressor 2 Water Circuit – A (Range A or B)
Split Wtr Cond – Split Water Condenser – No or Yes
Air Cool Type – Mechanical Air Cooling Type – None, ACC (Air-Cooled Condenser),
WCC (Water Cooled Condenser, or CHW (Chilled Water Coil)
Max EF Vol – Maximum Exhaust Fan Volume – 32.6 kCFM (Range 0 to 99.9)
Pool Wtr Cond – Pool Water Condenser Type – Full or Partial or None.
Exhaust Fan Inst – Exhaust Fan Installed in unit – No or Yes
Purge Fan Inst – Purge Fan Installed in unit – No or Yes
Spc Press Sen Inst – Space Pressure Sensor Installed in space – No or Yes
Rtn CO2 Sen Inst – Return Air CO2 Sensor Installed – No or Yes
MultiUnit Control – No, set to Yes for multi-unit networking
Rem Exh Fan Ins – Remote Exhaust Fan Installed – No or Yes
CW/HW DH Mode – Chilled Water/Hot Water Dehumidification Mode installed – No or Yes
Fan Speed Ctl Type - EC or VFD
Supply Fan – Supply Fan Configuration
Run Cur Tol – Fan Proof Current – 002.5 A (Range 0 to 999.9) D cabinet only
Run Cur Dly – Time Delay to Prove Current – 05 s (Range 0 to 99) D cabinet only
Flow Ctl – Airflow Control Mode
CFM Setp – This mode indicates that the fan speed or outside air damper position will be controlled to maintain
airflow at CFM set points.
Spd Setp – This mode indicates that the supply fan speed will be controlled by setting the supply fan
RPM set points.
If Spd Setp selected, set the below setpoints:
Occ Speed – Fan Speed during Occupied Mode – 1752 RPM (Range 30 to 1800)
Unocc Speed – Fan Speed during Unoccupied Mode – 1402 RPM (Range 30 to 1800)
Purge Speed – Fan Speed during Purge Mode – 1752 RPM (Range 30 to 1800)
If CFM Setp selected, set the below setpoints:
Occ Flow – Occupied Mode Airflow – 30.0 kCFM (Range 0 to 70)
Unocc Flow – Unoccupied Mode Airflow – 24.0 kCFM (Range 0 to 70)
Purge Flow – Purge Mode Airflow – 30.0 kCFM (Range 0 to 70)
Min Ctl Spd – Minimum Control Speed – 540 RPM (Range 0 to 2000)
Max Ctl Spd – Maximum Control Speed – 1950 RPM (Range 0 to 3000) Contact Factory before adjusting
the below values:
Ctl Dband – Control Deadband – 00.0 kCFM (Range 0 to 10.0)
Unit Configuration

Table of Contents

Other manuals for PoolPak MPK series