© 2017 PoolPak LLC. All rights reserved. MPK Series - Installation, Operation and Maintenance | 43
PoolPak
®
MPK Series IOM
Figure 4-6. Negative Pressure Condensate Drain Piping Cross Section
Figure 4-7. Positive Pressure Condensate Drain Piping Cross Section
UNIT BASE
MINIMUM SCHEDULE 40 PVC
REMOVABLE
CLEANOUT
OPEN TEE
FOR VENT
NOTE: NOT TO SCALE
MPK UNIT
PLUG THE
UNUSED
CONNECTION
WITH SUITABLE
PVC PLUG
1
2
4 INCHES MINIMUM OR MAX NEGATIVE STATIC
PRESSURE (INCHES W.C.) + 1 INCH
2 INCHES MINIMUM OR 1/2
1
1
2
UNIT BASE
NOTE: NOT TO SCALE
1/2 INCH MINIMUM
MAX POSITIVE STATIC PRESSURE (INCHES W.C.) + 1/2 INCH MINIMUM
MINIMUM SCHEDULE 40 PVC
REMOVABLE
CLEANOUT
OPEN TEE
FOR VENT
1
1
2
2
PLUG THE
UNUSED
CONNECTION
WITH SUITABLE
PVC PLUG
MPK UNIT