Appendix IV
144
Appendix I
V
high pressure reached value of this parameter,
the I / O output terminal select 25, then it will
output arrival signal.
E06
Low pressure arrival
60%
when feedback pressure less than the low
pressure reached value of this parameter, the I
/ O output terminal select 26, then it will
output arrival signal.
E07
Regular time water supply
0
Regular time water supply function invaid
Multi-function constant pressure water supply pump specific parameters
Parameter
Keyboard display
setting
Meaning
E08
E08 regular rotation
interval
0.25
According first start first stop principles to
control pump rotation, rotation time of 0.25
hours
E09
Electromagnetic
switching action delay
0.500
When set up a station pump (drive motor) to
switch from variable frequency industry
frequency , or from industry frequency to
variable frequency, and set its electromagnetic
switching action delay time is 0.5 seconds.
E10
Pump switch to judge
the time
100
To set the determine time 100 seconds from
inverter output frequency reaches the upper
limit frequencies until increase pump (drive
motor); or from inverter output frequency
reaches the lower limit frequencies until
decrease pump (drive motor).
E11
Constant pressure water
supply configuration
0
Shutdown: When the inverter failure,the
rotation switching way is from variable
frequency pump to industry frequency and
the pump maintain the status.
E12
Multi-pump configuration
0000
N. 1 ~ 3 pumps are frequency controlled
pump, pump 4 is soft-starter controlled pump.
E13
Multi-pump status
1112
Multi-pump control mode, displays the status
of each pump
E14
Soft-start pump control
Multi-pump control mode, set the control
mode of each pump, i currently set to Full
Stop
Constant pressure water supply IO parameters:
Parameter
Keyboard display
setting
Meaning
o21
o1 input signal select 1
25
High pressure arrival
o22
o2 input signal select 2
26
Low pressure arrival
o23
o3 input signal select 3
1
Fault input alarm
o36
(DI1) input terminal
function selection
1
FWD
o37
(DI2)input terminal
function selection
39
Free parking