Section V Parameter Function Table
41
Section V
Current limitation function can effectively restrain over-current caused by motor load
fluctuation in the process of acceleration and deceleration or constant speed operation.
This function will be good effect for V/F control mode.
Under protection of current lost- speed state, the motor speed will drop. so it is not adapted
by system which is not allowed to automatically drop speed.
In operation process, when the motor current surpass value A16 set, motor will decelerate
according to deceleration time A15 set until current below value A16 set.
In operation process, when the motor surpass value A17 set, motor will run with this speed
until current below value A17 set.
Deceleration current limitation is prior of constant speed limitation.
Series
Current limitation%
Corresponding parameter
F
120
A17
130
A16
G
150
A17
170
A16
A18
Output phase lose protection
N protection of phase lost
0
-
0
Y
Warning and constant
running
1
Warning and deceleration
2
Warning and free stopping
3
A19
Grade of phase lose
protection
10~100
%
30
Y
When ratio of unbalance 3phase output surpass A19 Grade of phase lose protection, the
inverter output phase lose protection i will action, and the system display fault PH-O.
Output frequency less than 2.00Hz, there is N output phase lose protection.
Phase lost protection grade=max current difference between phases, which will be according
to load condition.
A20
Over torque inspected action
N torque inspection
0
-
0
Y
Warning and running
1
Warning and decelerating
stop
2
Warning and free stopping
3
A21
Over torque grade
10~250
%
Y
A22
Over torque inspection time
0.0~60.0
s
0.1
Y
Motor output current surpass value A21 set, Over torque inspection will be force and the
system will show OL2 fault.
Series
Over torque inspection class
Parameter
F
130
A21
G
170
A21
A23
Electronic thermal relay
N
0
-
1
Y

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Powtran PI8600 Series and is the answer not in the manual?

Powtran PI8600 Series Specifications

General IconGeneral
BrandPowtran
ModelPI8600 Series
CategoryInverter
LanguageEnglish

Related product manuals