1 bit : Stop mode
0 All slow down, all pumps in turn slowing down.
1 Variable frequency pump stop:variable frequency pump stop running,variable frequency
pump and soft start pump under frequency keep running.
Stop power frequency pump,you need to use o36~o46parking command or keyboard input
terminal free multi - function keys MF1, MF2 set to 2 : Free Parking function.
2 Free stop, all pumps free stop
After free stop,E11 1000bit pump reset according to the order start and stop,but reorder
according to E12 multi - pumps configuration.
3 Water supply pump stops,only those constant pressure water supplying pumps stop,soft
start pump keep running under pump frequency.
Stop soft - starting pump, you need to use stop command of the soft star pump for o36 ~ o46
input terminal or keyboard multi - function keys MF1, MF2 set to 2 : Free stop function.
10 bit: Treatment under fault pump states
0 Maintain the status quo, when inverter failure, stop the current variable frequency pump
operation and other power - frequency operation of variable frequency pump and soft start
pump maintain the status
Fault occurs, if the following breakdown, select fault treatment according to failure action.
The feature only applies to the fault under the mode allowing fault runs. The fault is not
allowed to run, all stop.
1 All pump stop, when inverter failure, all pumps free stop.
100 bit: Soft start switching mode
0 Convert frequency to power frequency, frequency control of the pump current increases
the speed to the frequency, the rotation of the pump start and stop switch control or soft start