Read only parameters
Submenu
Explanation, further submenus
Value
11-18
manufacturing
number
Manufacturing date, type, serial number of the equipment and description of the options.
11-18-1 year, month
pl.: 1208
11-18-2 power
pl.: 7,50 kW
11-18-3 serial number
pl.: 426
11-18-4 option
pl.: DC 700 V
11-18-5 voltage
pl.: 400 V
11-18-6 type
pl.: VLD
11-19
version
Version number of the program loaded in the equipment and the identifier of the hardware.
11-19-1 software
pl.: 8.94.11
11-19-2 hardware
(information necessary for the manufacturer)
Date
Submenu
Explanation, further submenus
Values
Default setting
Unit
11-20
date
This setting has to be made carefully for the right use of the intervals and the logging of the events
and errors!
11-20-1 year
2006 - 2099
2006
11-20-2 month
1 - 12
1
11-20-3 day
1 - 31
1
11-20-4 days
Monday
Tuesday
Wednesday
Sunday
Monday
11-20-5 hour
0 - 23
0
11-20-6 minute
0 - 59
0
11-20-7 second
0 - 59
0
System parameters changeable with the manufacturer password
Submenu
Explanation, further submenus
Values
Default setting
Unit
11-21
currents
This item permits the calibration of the frequency converter's current measuring unit, and the setting
of the limit currents to be used at different temperatures. Each of them is I peak value!
11-21-1 I measuring range
type-dependent
type-dependent
A
11-21-2 I inverter limit t=40 C
type-dependent
type-dependent
A
11-21-3 I inverter limit t=80 C
type-dependent
type-dependent
A
11-21-4 I inverter maximum
type-dependent
type-dependent
A
11-22
voltages
Internal voltages of the frequency converter
11-22-1 Umin
type-dependent
type-dependent
V
11-22-2 Ustart
type-dependent
type-dependent
V
11-22-3 Udecel.
type-dependent
type-dependent
V
11-22-4 Uaccel.
type-dependent
type-dependent
V
11-22-5 Umax
type-dependent
type-dependent
V
11-23
special data
Internal parameters of the frequency converter.
11-23-1 cooling fan switch on
0 - 90
45
C
11-24
clear log
Serves to clear the event log, the error log,
operation hours1, operation hours2 and the
consumption meters!
clear

Table of Contents