7 PROFIBUS DP Extensions
66
Revision 1.04
VPC3+S User Manual
Copyright © profichip GmbH, 2012
Byte
Bit Position
Designation
7
6
5
4
3
2
1
0
0
Structured_Length
1
0
0
0
0
0
1
1
1
Structure_Type
2
0
0
0
0
0
0
0
0
Slot_Number
3
0
0
0
0
0
0
0
0
Reserved
4
0
0
0
0
0
0
0
1
Version
5
Publisher_Addr
6
Publisher_Length
7
Sample_Offset
8
Dest_Slot_Number
9
Offset_Data_Area
10
Sample_Length
11
:
120
further link entries
Figure 7-9: Format of the Structured_Prm_Data with DXB Subscribertable
(specific link is grey scaled)
The user must copy the link entries of DXB Linktable or DXB
Subscribertable, without Dest_Slot_Number and Offset_Data_Area, into the
DXB_Link_Buf and set R_Len_DXB_Link_Buf. Also the user must enter the
default status message in DXB_Status_Buf with the received links and
write the appropriate values to R_Len_DXB_Status_Buf. After that, the
parameterization interrupt can be acknowledged.