Fault description Cause Remedy Personnel
No. 5: The identifier and the message
‘Fan warning’
appear.
The fan is faulty or not con‐
nected.
Return the pump to
ProMinent.
Instructed per‐
sonnel
No. 12: The identifier
and the mes‐
sage
‘Invalid metering volume’
appear.
The set metering volume in con‐
centration mode cannot be
metered.
Adapt the metering
parameters.
Technical per‐
sonnel
No. 13: The identifier
"Temperature"
and the message
‘Temperature’
appear.
The temperature is too high. Rectify the cause.
The pump starts up
automatically.
Technical per‐
sonnel
16.2.3 All other faults
Please contact the responsible ProMinent branch or representative!
16.3
Log book
16.3.1 Fault messages in the log book
For more information on the ‘ERROR’ messages - refer
to the chapter "Fault messages on the LCD screen”.
Tab. 20: Errors
Log book no. Description Acknowledge?
0 System, EEProm error* X
1 The pump is in
‘Analog’
operating mode, a fault behaviour has been
programmed in the
‘Analog’
menu and the control current has fallen
below 4 mA.
-
2 The pump is in
‘Analog’
operating mode, a fault behaviour has been
programmed in the
‘Analog’
menu and the control current has risen
above 20 mA.
-
3 The fluid level in the storage tank has reached "Liquid level low 2nd
stage".
-
4 The pump hose has a leak. -
5 The state of the dosing monitor is not as expected. X
6 - -
7 The ambient temperature is too high or too low. -
8 - -
9 - -
10 An incorrect parameter has been entered. X
11 - -
12 - -
13 The mains voltage is too low or not connected. -
14 - -
15 - -
16 The memory for revolutions, which have not yet been processed, has
overflowed.
X
Troubleshooting
92