Tab. 3: Control via:
Switching element Specification
potential-free contact Load: 0.5 mA at 5 V
Semiconductor switch Residual voltage < 2 V
Parameter Value
Max. pulse frequency 50 pulses/s
Min. pulse duration 10 ms
Tab. 4
Switching element Specification
NPN output (Open Drain) 30 V max. voltage and 300 mA
max. current load per pin
CAUTION!
No protection provided for inductive loads.
Provide a free-running diode when controlling a
delay.
9.2.2 "External control" terminal
The "external control" terminal is a 5-pole panel terminal. It is compatible
with 2- and 4-pin cables.
Only use a 5-pin cable with the "Auxiliary capacity" and "mA input" func‐
tions.
Electrical interface for pin 1 "Pause" - pin 2 "External contact" - pin 5 "Aux‐
iliary capacity"
Data Value Unit
Voltage with open contacts 5 V
Input resistance 10 kΩ
Max. pulse frequency 25 pulse/s
Min. pulse duration 20 ms
Control via:
n potential-free contact (load: 0.5 mA at 5 V) or
n semiconductor switch (residual voltage < 0.7 V)
Electrical interface for pin 3 "mA input" (with identity code characteristic
"Control version": 2 and 3)
1
Data Value Unit
Input load, approx. 120
1
The metering pump starts running at approx. 0.4 mA (4.4 mA) and rea‐
ches maximum capacity at approx. 19.6 mA.
Configured as an output
1
54
2
3
P_BE_0014_SW
Fig. 12: Assignment on pump
Installation, electrical
32

Table of Contents

Other manuals for ProMinent DULCO flex Control

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent DULCO flex Control and is the answer not in the manual?

ProMinent DULCO flex Control Specifications

General IconGeneral
BrandProMinent
ModelDULCO flex Control
CategoryWater Pump
LanguageEnglish

Related product manuals