Specification for fire doors
23
102-127108955 V1.1 95/ 102
Parameter setting for utilisation on fire doors
Parameter Factory default Change configuration to
DOOR SYSTEM
Fire alarm Disabled Enabled
NOTICE
For parameter setting please also see chapter
Configuration
!
Hints for low-energy operators
NOTICE
The fire door and low-energy operator combination is only authorised according
to the data shown in the table below.
Arm type Maximum authorised door closers - according to size
EN 4 EN 5 EN 6
Standard arm authorised not authorised not authorised
Slide arm pulling authorised not authorised
Slide arm pushing authorised not authorised
Ü-designation
Hold-open system for bi-parting doors (master / slave)
The Master/Slave function ensures appropriate closing sequence in normal operation mode.
For the fault "power failure" a mechanical closing sequence control must always be used.
NOTICE
For parameter setting please refer to chapter
Configuration
!
Acceptance of hold-open system
IMPORTANT
Acceptance, tests and maintenance should only be carried out by a specialist or
a person specifically trained for that. The authorization of these persons exclu-
sively lies with the manufacturer of the hold-open system. Extent, results and
time of the periodical inspection must be recorded. These records must be kept
by the operator.
23.4
23.5
23.6
23.7
23.7.1