Loading...
page 10 of 91 USB-QFLCII-14804/0
Unit
Q-FlapCompact II / Q-FlapCompact II plus series /
DN
DN
140
160
200
250
280
315
355
400
Maximum Kst value
bar x
m/s
200 200 200 200 200 200 200 200
Minimum mounting
distance dust
explosion class St 1
m
2.6
2
2
2
2
2
2.6
2.6
ft. 8.53 6.56 6.56 6.56 6.56 6.56 8.53 8.53
Maximum mounting
distance dust
explosion class St 1
m
6.6
7
7
7
7
7
6.6
6.6
ft. 21.65 22.97 22.97 22.97 22.97 22.97 21.65 21.65
Unit
Q-FlapCompact II / Q-FlapCompact II plus series /
DN
DN
450
500
560
630
710
800
900
1000
Maximum Kst value
bar x
m/s
200 200 200 200 200 200 200 200
Minimum mounting
distance dust
explosion class St 1
m
2.6
2.6
2.6
3
3
3
3
3
ft. 8.53 8.53 8.53 9.84 9.84 9.84 9.84 9.84
Maximum mounting
distance dust
explosion class St 1
m
6.6
6.6
6.6
7
7
7
7
7
ft. 21.65 21.65 21.65 22.97 22.97 22.97 22.97 22.97
Unit
Q-FlapCompact II / Q-FlapCompact II plus
series / DN
DN
140
160
200
250
280
315
Maximum Kst value
bar x
m/s
200 200 200 200 200 200
Minimum mounting
distance at St 1
aluminum dust (no
heating value
restriction)
m 3.5 3.5 3.5 3.5 3.5 3.5
ft. 11.48 11.48 11.48 11.48 11.48 11.48
Maximum mounting
distance dust
explosion class St 1
aluminum dust (no
heating value
restriction)
m 4.5 4.5 4.5 4.5 4.5 4.5
ft. 14.76 14.76 14.76 14.76 14.76 14.76
Unit
Q-FlapCompact II / Q-FlapCompact II plus
series / DN
140
160
200
250
280
315
Maximum Kst value
300 300 300 300 300 300
Minimum mounting
distance at dust
explosion class St 2
m 3.6 3.5 3.5 3.5 3.5 3.5
ft. 11.81 11.48 11.48 11.48 11.48 11.48
Maximum mounting
distance at dust
explosion class St 2
m 7 7.5 7.5 7.5 7.5 7.5
22.97
24.61.
24.61
24.61
24.61
24.61
Mounting
distance for dust
explosion class1
sizes
DN 140 (5.51’’) to
DN 400 (15.75’’)
Mounting
distance for dust
explosion class1
sizes
DN 450 (17.72’’)
to DN 1000
(39.37’’)
Mounting
distance for
aluminum dust
explosion class1
(no heating value
restriction))
Mounting
distance at dust
explosion class 2

Table of Contents