6.3 Mounting distances and measures
Unit
Q-FlapCompact II / Q-FlapCompact II plus series /
DN
160
200
250
280
315
355
400
Minimum mounting
distance for dust
explosion class St1
2
2
2
2
2
2.6
2.6
ft 8.53 6.56 6.56 6.56 6.56 6.56 8.53 8.53
Maximum mounting
distance for dust
explosion class St1
7
7
7
7
7
6.6
6.6
ft 21.65 22.97 22..97 22.97 22.97 22.97 21.65 21.65
Required straight
duct between inlet
isolation device and
eclosure (approx..)
800
1000
1250
1400
1575
1775
2000
in. 27.56 31.50 39.37 49.21 55.12 62.01 69.88 78.74
Inspection lid range
420
460
480
520
540
590
645
in.
16.54 18.11
18.90
20.47
21.26
23.23
25.39
Unit
Q-FlapCompact II / Q-FlapCompact II plus series /
DN
DN
450
500
560
630
710
800
900
1000
Minimum mounting
distance for dust
explosion class St1
m
2.6
2.6
2.6
3
3
3
3
3
ft 8.53 8.53 8.53 9.84 9.84 9.84 9.84 0.12
Maximum mounting
distance for dust
explosion class St1
m
6.6
6.6
6.6
7
7
7
7
7
ft 21.65 21.65 21.65 22.97 22.97 22.97 22.97 275.59
Required straight
duct between inlet
isolation device and
eclosure (approx..)
mm
2250
2600
2600
3000
3000
3000
3000
3000
inch 88.58 102.36 102.36 118.11 118.11 118.11 118.11 118.11
Inspection lid range
mm
700
760
820
880
950
1060
1190
1310
inch
27.56
29.92
32.28
34.65
37.40
41.73
46.85
51.57
Mounting
distance for dust
explosion class 1
from
DN 140 (5.51’’) to
DN 400 (15.75’’)
Mounting
distance for dust
explosion class 1
from
DN 450 (17.72) to
DN 1000 (39.37’’)