Reference Manual
00809-0100-4130, Rev AA
May 2009
A-3
Rosemount 2130
Minimum and Maximum Operating Temperatures
• See Figure A-2 for maximum and minimum operating temperatures
Figure A-2.
Operating Temperatures
Liquid Density Range
• Minimum standard density is 37.5 lb/ft
3
(600 kg/m
3
)
• Minimum density is 31.2 lb/ft
3
(500 kg/m
3
) when ordered with the
Low Density Range option
Liquid Viscosity Range
• 0.2 to 10000 cP (centiPoise) when operating in the Normal mode
• 0.2 to 1000 cP (centiPoise) when operating in Self-check mode
Solids Content and Coating
• The maximum recommended diameter of solid particles in the liquid is
0.2 in. (5 mm) when used in normal mode only
• For coating products, avoid bridging of forks
Switching Delay
• There is a user-selectable 0.3, 1, 3, 10, 30 seconds delay for dry-to-wet
and wet-to-dry switching
CIP (Clean In Place) Cleaning
• The 2130 withstands steam cleaning routines
Electrical Switching Mode
• User-selectable switching mode (Dry = on or Wet = on)
Protection
• Polarity insensitive
• Over-current protection
• Short-circuit protection
• Load-missing protection
• Surge protection (to IEC61326)
Terminal Connection (Wire Diameter)
• Maximum 0.1 in
2
(2,5 mm
2
) – Note national regulations
176 (80)
176
(80)
-40 (-40)
-94
(-70)
500
(260)
Process Temperature °F (°C)
Ambient Temperature °F (°C)
149 (65)
32 (0)
32
(0)
The 2130