Rosemount 2130
Minimum and Maximum Operating Temperatures
See Figure A-2 for maximum and minimum operating temperatures
Figure A-2.
Operating Temperatures
Liquid Density Range
Minimum standard density is 37.5 lb/ft
3
(600 kg/m
3
)
Minimum density is 31.2 lb/ft
3
(500 kg/m
3
) when ordered with the
Low Density Range option
Liquid Viscosity Range
0.2 to 10000 cP (centiPoise) when operating in the Normal mode
0.2 to 1000 cP (centiPoise) when operating in Self-check mode
Solids Content and Coating
The maximum recommended diameter of solid particles in the liquid is
0.2 in. (5 mm) when used in normal mode only
For coating products, avoid bridging of forks
Switching Delay
There is a user-selectable 0.3, 1, 3, 10, 30 seconds delay for dry-to-wet
and wet-to-dry switching
CIP (Clean In Place) Cleaning
The 2130 withstands steam cleaning routines
Electrical Switching Mode
User-selectable switching mode (Dry = on or Wet = on)
Protection
Polarity insensitive
Over-current protection
Short-circuit protection
Load-missing protection
Surge protection (to IEC61326)
Terminal Connection (Wire Diameter)
Maximum 0.1 in
2
(2,5 mm
2
) – Note national regulations
176 (80)
176
(80)
-40 (-40)
-94
(-70)
500
(260)
Process Temperature °F (°C)
Ambient Temperature °F (°C)
149 (65)
32 (0)
32
(0)
The 2130