EasyManua.ls Logo

Rosemount 8732 - Series 1800 (Version 2) Sensor to Rosemount 8732 Transmitter

Rosemount 8732
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
E-16
Series 1800 (Version 2)
Sensor to
Rosemount 8732
Transmitter
Connect coil drive and electrode cables as shown in Figure E-13.
Figure E-13. Wiring Diagram for
Foxboro Series 1800 (Version 2)
and Rosemount 8732
Table E-14. Foxboro Generic
Sensor Wiring Connections
FOXBORO SERIES
1800 SENSOR
(VERSION 2)
ROSEMOUNT
8732
TRANSMITTER
Coil Connections
Electrode
Connections
GND L2
L1
White
Black
Shield
Rosemount 8732 Foxboro Series 1800 Sensors
1L1
2 L2
Chassis Ground
17 Any Shield
18 Black
19 White
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor
or to terminals 1 and 2 of the
transmitter, or replacement of the
electronics board will be necessary.

Table of Contents

Related product manuals