46
-
8000B Series
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modi-
cation
Type
F5.06
~
F5.09
Reserved
F5.10
On/off filter
times
1~10 5
F5.11
FWD/ REV
control mode
0:2-wire control mode 1
2:2-wire control mode 2
3:3- wire control mode 1
4:3- wire control mode 2
0
F5.12
Frequency
change rate
when UP/
DOWN setting
0.01~50.00Hz/s 0.01Hz/s 0.50Hz/s
F5.13 AVI lower limit 0.00V~10.00V 0.01V 0.00V
F5.14
AVI lower limit
corresponding
to setting value
-100.0%~100.0% 0.1% 0.0%
F5.15 AVI upper limit 0.00V~10.00V 0.01V 10.00V
F5.16
AVI upper limit
corresponding
to setting value
-100.0%~100.0% 0.1% 100.0%
F5.17
AVI input filter
time
0.00s~10.00s 0.01s 0.10s
F5.18 ACI lower limit 0.0mA~20.0mA 0.1mA 4.0mA
F5.19
ACI lower limit
corresponding
to setting value
-100.0%~100.0% 0.1% 0.0%
F5.20 ACI upper limit 0.0mA~20.0mA 0.1mA 20.0mA

Table of Contents