Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modi-
cation
Type
F6.04
FM output
selection
0:Running frequency
1:Setting frequency
2:Running rotation speed
3:Output current
4:Output voltage
5:Reserved
6:Reserved
7:Reserved
8: Analog AVI input value
9: Analog ACI input value
0
F6.05
FM output lower
limit
0.0~100.0% 0.1% 0.0%
F6.06
FM lower limit
corresponding
to output
0.00V~10.00V 0.01V 0.00V
F6.07
FM output upper
limit
0.0~100.0% 0.1% 100.0%
F6.08
FM upper limit
corresponding
to output
0.00V~10.00V 0.01V 10.00V
F6.09
AM output
selection
0:Running frequency
1:Setting frequency
2:Running rotation speed
3:Output current
4:Output voltage
5:Reserved
6:Reserved
7:Reserved
8: Analog AVI input value
9: Analog ACI input value
0
F6.10
AM output lower
limit
0.0~100.0% 0.1% 0.0%
F6.11
AM lower limit
corresponding
to output
0.00V~10.00V 0.01V 0.00V

Table of Contents