Troubleshooting
Samsung Electronics 209
4-3 Appropriate Measures for Different Symptom (cont.)
4-3-47 COMP Overcurrent error (cont.)
Continue Continue
Before change / After change
Error, depending on the situation replace
the Compressor or PBA
■ Compressor applied one ■Compressor applied two
Restart
Inverter1- Compressor2
Inverter2- Compressor1 to the wiring change
Power Off
Replace Inverter PBA
Before change After change Measure
E464 E464 Replace No.1Inverter PBA
E464 E364 Replace No.1 Compressor
E364
E364 Replace No.2 Inverter PBA
E364
E464 Replace No.2 Compressor
See the "Contain of compressor Exchange (3-XX)" in service manual when you replace the compressor.