EasyManua.ls Logo

Samsung AM080FX A Series - Case Study - E206 (Internal Communication Error of the Outdoor Unit C-Box)

Samsung AM080FX A Series
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 233
4-4-7 Case study – E206 (Internal communication error of the outdoor unit C-box)
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation Defrost Timer Fan
Filter/
MPI
Operation Defrost Timer Filter Operation Timer Turbo
24 27
× × × × × × × ×
※ ● : ON : Flash ×: OFF
Judgment
Method
∙ PBA does not respond to the invoked Main PBA
Cause of
problem
∙ C-Box internal Inverter PBA, Fan PBA, Hub PBA defective
Possibility
1) Poor connection of communication wiring and connector
2) Defect of related electric component
* Reference
E206- C001 : HUB PBA communication error / E206-C002 : FAN PBA communication error
E206- C003 : INV1 PBA communication error / E206-C004 : INV2 PBA communication error
E206- C005 : Water Hub PBA communication error
Main PBA Hub PBA Inverter PBA
4-4 Case study for trouble shoots (cont.)

Table of Contents