Piping Diagram
Samsung Electronics 368
Emergency operation for compressor malfunction
▪ Purpose
Perform emergency operation until servicing if there is compressor failure when using more than one compressor.
▪ Concept
Faulty compressors are disabled and turned off.
▪ Control specifications in detail
Disabled compressors are excluded from capacity distribution, heat treatment of winding wire, protective control, and
self-diagnosed error detection.
▪ Notes
- The performance may degrade if this option is changed.
- Make sure to return the option to the default value after servicing the compressor.
- Error E560 will be triggered if all the compressors on outdoor units are disabled.
(The SVC V/V must be closed for outdoor units if modules are installed and all the compressors on a single
outdoor unit are disabled.)
Setting Outdoor Seg1 Seg2 Seg3 Seg4 Emergency operation for compressor malfunction
Individual 0 0
0 0 Disabled (Default)
0 1 Set compressor 1 as malfunction state
0 2 Set compressor 2 as malfunction state
7-3 Functions (cont.)
7-3-3-1 Field Setting
7-3-3 Others