Piping Diagram
Cold Air Prevention
Purpose
Control the fan speed to avoid discomfort of people in the room due to cold air in cooling mode or during the initial start-
up of heating.
Concept
- The fan does not operate if the indoor heat exchanger temperature is low in heating mode.
The fan speed is restricted if the temperature is low.
Control specifications in detail
- Condition(s) required to use the mode : Indoor units are operating in heating mode
- The fan speed is restricted according to the average heat exchanger temperature and temperature variations
(increase/decrease).
Evap. avg. Temp.
Airflow in heating mode
If the temp rises
If the temp drops
High or lower
High or lower
38
36
34
32
30
28
26
20
Mid or lower
Mid or lower
Low
Low
Low Low
Fan off
Low Low
7-3 Functions (cont.)