Troubleshooting
Samsung Electronics 229
4-4-4 Vacuum
Operation to facilitate vacuum to open the valve after the Outdoor Unit repair.
There are several EEV & solenoid valve so to secure perfect vacuum this function is required.
K1 button Display on 7-Segment Function
7times
“
” “ ” “ ” “ ”
Vacuuming( Outdoor unit address 1)
8times
“
” “ ” “ ” “ ”
Vacuuming( Outdoor unit address 2)
9times
“
” “ ” “ ” “ ”
Vacuuming( Outdoor unit address 3)
10times
“
” “ ” “ ” “ ”
Vacuuming( Outdoor unit address 4)
11times
“
” “ ” “ ” “ ”
Vacuuming(All outdoor units)
How to lnitiate K1 Tact Swithc 7 times~11 times
Compressor OFF
Indoor Unit/Outdoor Unit OFF
4Wasy Valve OFF
Valve Open all valves maximum
Etc. If not turn off the vacuum mode, the start of normal operation is prohibited.
4-4 Case study for trouble shoots (cont.)