EasyManua.ls Logo

Samsung AM080FX A Series - Page 347

Samsung AM080FX A Series
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Piping Diagram
Samsung Electronics 366
Drain Pump Control
Purpose
Discharge the condensate stagnating in the indoor unit's drainage plate to prevent the condensate from overflowing
indoor units.
Concept
If the amount of condensate stagnating in the drainage plate reaches a certain level where it may overflow, the Float soft-
ware detects this and activates the drain pump to discharge the condensate to the outside via the hose.
Control specifications in detail
Condition(s) required to use the mode : The Drain Pump Option is used, or the model name
(Rem_Opt) is set to 1-Way, 2-Way, or 4-Way
Drain Pump ON : (Cooling or Auto cooling or Dehumidifying mode ON) and
(Outdoor Comp ON) and (Indoor unit Thermo-ON)
Thermo-ON
Thermo-OFF
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pump OFF
Cooling or Auto cooling or
Dehumidifying mode
Drain Pump OFF : (Operation OFF) or (Indoor unit Thermo OFF)
Thermo-ON
Thermo-OFF
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pump OFF
If 3-min delay option (Rem_Opt) is on
Cooling or Auto cooling or
Dehumidifying mode
Notes
The drain pump activates if the Float S/W operates in heating mode
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pump OFF
Cooling or Auto cooling or
Dehumidifying mode
7-3 Functions (cont.)
7-3-2-6 Indoor unit control (cont.)
7-3-2 Control (cont.)

Table of Contents

Related product manuals