Troubleshooting
Samsung Electronics 235
4-4-9 Case study – E108, E604, E613
PIM display E604
Contents Communication error between wired remote controller & Indoor unit
Error result Remote controller stop
Cause
- When tracking between wired remote controller and
indoor unit/ventilator (ERV) is not complete for more than
3 minutes( ex: System communication error like E201, E108…)
- IDU address has been changed after wired remote controller
tracking completion
Treatment
1) Power reset of Wired Remote controller
(Manual reset ; re connect the power wire)
PIM display E613
Contents Error which occurs when there is no communication between DMS and PIM/SIM for 15 minutes
Error result PIM stop
Cause
- System communication error like E201, E108
- Wired disconnection
Treatment
- System communication error fix
- Check the wire
Error code Description Cause Solution
E613
Comm. error between
DMS and PIM/SIM
Comm. was not finished
Because of E108
Fix E108
E108
Address duplication of IDU/MCU/EEV
kit
EEV KIT address setting
Failure (human error)
Fix IDU address
E604
Tracking error between remote con-
troller and the IDU
Tracking fail because of E108
Power reset on
Wired remote controller
4-4 Case study for trouble shoots (cont.)