Wiring Diagram
Electrical wiring work (cont.)
Specification of Cable and Connecting method
- For communication cable, 2-core sheathed vinyl cable should be used which satisfies nominal area of 0.75~1.25 thickness. If 2 or more than
3 communication are connected with one cable which is 4, 6 or more strands, communication malfunction could be caused. Only 2-core sheathed vinyl cable
should be used for one communication line.
- Maximum connecting length is limited to 1,000m, so you should follow this limit not to cause malfunction of communication.
- Maximum number of units that can be connected to the outdoor main unit is 64, so do not exceed this limit.
- Communication cable should be connected in series as in the picture below, and malfunction of communication can be occur if many units are connected to
the same terminal.
- Communication cable between indoor and outdoor units and communication cable between outdoor units has no polarity.
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
High Temperature & pressure Gas
High Temperature & pressure Liquid
Low Temperature & pressure Gas
Low Temperature & pressure Liquid
HEAT
FAN ON
Ball Valve -
Gas pipe (BV_G)
Outdoor Fan Motor 1
(OFM1)
Outdoor Fan Motor 2
(OFM2)
Thermistor - Ambient (T_A)
Thermistor -
Cond Out (T_CO)
Heat Exchanger - Main (HX_M)
Thermistor - Suction pipe (T_S)
Check Valve -
EEV Bypass (CV_EB)
Electronic Expansion
Valve - Main (E_M)
IPM Cooler 1
(IPMC1)
IPM Cooler 2
(IPMC2)
Heat Exchanger -
Intercooler (HX_IC)
Thermistor -
EVI In (T_EI)
Thermistor -
Liquid pipe (T_L)
Electronic
Expansion
Valve -
EVI (E_EVI)
Thermistor -
EVI Out (T_EO)
Solenoid Valve -
EVI Bypass
(V_EB)
Ball Valve -
Liquid pipe (BV_L)
Solenoid Valve -
Accumulator oil Return (V_AR)
Pressure Sensor -
Low (PS_L)
Solenoid Valve -
Hot Gas bypass (V_HG)
(V_EVI2)
Solenoid
Valve -
EVI 1(V_EVI1)
Compressor 1
(COMP1)
(COMP2)
(T_D2)
(T_CT2)
Thermistor -
Discharge
pipe 1 (T_D1)
(PW_H2)
(OS2)
(CV_D2)
Oil Separator 1
(OS1)
Pressure Sensor -
High (PS_H)
Solenoid Valve - 4Way (V_4W)
Pressure
Switch -
High 1
(PW_H1)
Thermistor -
Compressor
Top 1
(T_CT1)
Check Valve -
Discharge 1
(CV_D1)
Accumulator
(AC)
HEAT
FAN ON
HEAT
FAN ON
OFF
FAN OFF
HEAT
FAN ON
OFF
FAN OFF
F1/F2
Indoor Outdoor communication line
OF1/OF2
Outdoor Outdoor communication line
R1/F2
Solution Outdoor communication line
6-8 Field Wiring (cont.)