EasyManua.ls Logo

Samsung AM080FX A Series - Page 333

Samsung AM080FX A Series
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Piping Diagram
Samsung Electronics 352
- If the compression ratio is low,
1st step Increase of the superheat degree : The superheat degree for compressor suction is increased .
2nd step Increase of the minimum compressor frequency : The minimum compressor frequency is increased to the predefined
model-specific frequency.
3rd step Comp Trip : If in critical state for 10 min, stop the compressors and trigger an error (E428).
Normal Operation
Cooling : Target SH 6 K & Target HP 28kgf/ cm
2
,g
Heating : Target S H 4 K
Cooling : Minimum Hz increases if in this state for 3 min
Compressor trip (E428) occurs if in this state for 10 min
SH control & Target HP release
Min Hz release
Compression ratio
※△ P =Hig h PressureLow Pressure
P kgf/cm
2
,g
or 1.5
1.7
1.9
P 8kgf/cm
2
,g
& 2.0
7-3 Functions (cont.)
7-3-2-5 Protective control (cont.)
7-3-2 Control (cont.)

Table of Contents

Related product manuals