EasyManua.ls Logo

Samsung AM080FX A Series - Page 335

Samsung AM080FX A Series
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Piping Diagram
Samsung Electronics 354
DSH (Discharge Super Heat) protection
Purpose
Prevent liquid compression to protect the system and compressors.
Concept
The compressor Suction Super Heat (SH) is raised to increase the DSH.
- DSH = Compressor discharge temp. – High pressure saturation temp.
- The compressor discharge temperature is defined during DSH protection control :
Min { Max(Tdis_comp1, Ttop_comp1), Max(Tdis_comp2, Ttop_comp2) }
Control specifications in detail
- The target superheat changes to 6 K if the DSH is 10 K or lower.
Enthalpy
Pressure
Ph-Diagram
Af ter DSH protection
Befo re DSH protection
DSH increase
SH increase
Normal Operation
10
15
20
DSH (K)
First heating release : the target SH is 3 K if in this state for 30 sec
Second heating release : SH release occurs 2 min after the first release
if the DSH is below 15 K
First cooling release : the target SH is 3 K if in this state for 30 sec
Second cooling release : SH release occurs 2 min after the first release if
the DSH is above 10 K
- If in this state for 30 sec,
Cooling : Indoor unit EEV Target SH 6 K
Heating : Main EEV Target SH 6 K
7-3 Functions (cont.)
7-3-2-5 Protective control (cont.)
7-3-2 Control (cont.)

Table of Contents

Related product manuals