EasyManua.ls Logo

Samsung AM080FX A Series - Page 343

Samsung AM080FX A Series
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Piping Diagram
Samsung Electronics 362
Temperature Compensation
Purpose
Compensate for variances in temperature affecting people differently in the room. Wind chill is caused by indoor tem-
perature stratification when using the internal temp sensors on indoor units instead of using external temp sensors in the
room.
Concept
If measuring the indoor temperature using the internal temp sensors on indoor units in heating mode, the temperature is
controlled under the assumption that the actual indoor temperature is lower than the temperature inside the indoor units
and the temperature difference is equivalent to the compensation temperature.
Control specifications in detail
Factory default (product option code SEG6)
- 4way type : T* = 5 K
- others : T* = 2 K
Installation setting( installation option code SEG21)
SEG21 Setting
T*
0 Factory default
1 2 K
2 5 K
* T : Heating compensation temperature
In case of using external room temp. sensor
( Installation option SEG4 = 1 ) :
T = 0
Notes
- Order of priority : Use of external temp sensor > Install offset > Basic option.
7-3 Functions (cont.)
7-3-2-6 Indoor unit control (cont.)
7-3-2 Control (cont.)

Table of Contents

Related product manuals