Samsung Electronics 381
Piping Diagram
Snow accumulation prevention control
Channel address
Purpose
Prevent snow accumulation on inactive outdoor units to ensure normal operation (default option).
Concept
Snow on top of outdoor units is removed by turning on outdoor fans if snow accumulation is detected by the snow sen-
sor or via the outdoor temperature.
Control specifications in detail
- If a snow sensor is not installed, the outdoor fans operate in 3step mode for one min every 30 min if operation stops at
an outdoor temperature of 5 or lower.
- If a snow sensor is installed and the sensor detects when operation stops at an outdoor temperature of 5 or lower,
the outdoor fans operate in 3 step for 10 sec and then continue operation in a higher step for 50 sec.
Purpose
Identify multiple main outdoor units connected to upper-level controllers, such as DMS and S-NET3.
Concept
- If the Channel address is set, the same channel address is assigned to the sub outdoor units,
indoor units, and MCUs connected to a main outdoor unit.
Control specifications in detail
Notes
- During snow accumulation, the fan may spin even when the unit is not in operation.
- Outdoor fans may be turned on by this feature during servicing. Careful attention is required.
Input unit Seg1 Seg2 Seg3 Seg4 Snow accumulation prevention control
Main 1 4
0 0 Enabled (default)
0 1 Disabled
Input unit Seg1 Seg2 Seg3 Seg4
Expand operational temperature range for
cooling operation (HR only)
Main 1 2
A U Automatic setting (default)
0 - 15
Manual setting for channel
0 - 15