Samsung Electronics 394
Key Options
8-4 How to check the view mode using a tact switch (cont.)
AM080~260SXVSSS
Optional item Input unit
SEG1 SEG2 SEG3 SEG4
Function of the option Remarks
Emergency operation
for compressor
malfunction
Individual 0 0
0 0 Disabled (Factory default)
E560 will occur when all the
compressors are set as
malfunction state.
0 1 Set compressor 1 as malfunction state
0 2 Set compressor 2 as malfunction state
Capacity correction
for cooling
Main 0 1
0 0 7-9 (Factory default)
Targeted evaporation temperature
[?C] (When low temperature value is
set, discharged air temperature of the
indoor unit will decrease)
0 1 5-7
0 2 9-11
0 3 10-12
0 4 11-13
0 5 12-14
0 6 13-15
Capcity correction
for heating
Main 0 2
0 0 3.0 (Factory default)
Targeted high pressure [MPa] (When
low pressure value is set, discharged
air temperature of the indoor unit will
decrease)
0 1 2.5
0 2 2.6
0 3 2.7
0 4 2.8
0 5 2.9
0 6 3.1
0 7 3.2
0 8 3.3
Current
restriction rate
Individual 0 3
0 0 100% (Factory default)
When restriction option is set,
cooling and heating
performance may decrease
0 1 0.95
0 2 0.9
0 3 0.85
0 4 0.8
0 5 0.75
0 6 0.7
0 7 0.65
0 8 0.6
0 9 0.55
1 0 0.5
1 1 No restriction
Oil collection interval Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
0 0 Factory default
0 1
Apply setting when the product is
being installed in humid area such as
near river or lake
Fan speed correction
for outdoor unit
Individual 0 6 0 0 Factory default
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
Enable the silent mode for
night-time
(Itoperates automatically
depending on the temperrature.)
However, if the external contact
ineterface module(MIM-B14) is used,
entering the silent mode is available
with contact signal
0 1 LEVEL 1/Auto
0 2 LEVEL 2/Auto
0 3 LEVEL 3/Auto
0 4 LEVEL 1/External contact
0 5 LEVEL 2/External contact
0 6 LEVEL 3/External contact
Long-piping condi-
tion setting (Setting is
unnecessary if
high-head condition
is set)
Main 0 9
0 0 Disabled (Factory default)
0 1 LEVEL 1
When equivalent length of farthest
indoor unit from the outdoor unit is
between 100~170m
0 2 LEVEL 2
When equivalent length of farthest
indoor unit from the outdoor unit is
over 170m
Energy saving setting Main 1 0
0 0 Disabled (Factory default)
0 1 Enabled
Energy saving mode triggers when
the room temperature reaches desired
temperature while
operating in heating mode.