Samsung Electronics 38
Product Specifications Product Specifications
Samsung Electronics 39
Image
Model Name AM140FXVAGH AM160FXVAGH AM180FXVAGH AM200FXVAGH AM220FXVAGH
Power Supply Φ, V, Hz 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50
Mode - HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP
Performance
HP HP 14 16 18 20 22
Capacity
(Nominal)
Cooling
kW 40.0 45.0 50.4 56.0 61.6
Btu/h 136,000 153,000 171,900 191,000 210,000
Heating
kW 45.00 50.00 56.70 63.00 69.30
Btu/h 153,000 170,000 193,500 215,000 236,000
Power
Power Input
(Nominal)
Cooling 1)
kW
8.90 11.00 12.80 15.19 17.35
Heating 2) 9.50 11.50 11.90 13.90 16.70
Current Input
(Nominal)
Cooling 1)
A
14.30 17.60 20.70 24.40 27.80
Heating 2) 15.20 18.40 19.10 22.30 26.80
Running Current
Cooling
A
14.30 17.60 20.70 24.40 27.80
Heating 15.20 18.40 19.10 22.30 26.80
Max 25.00 32.00 39.10 42.50 44.50
Power Consumption
Cooling 1)
kW
8.90 11.00 12.80 15.19 17.35
Heating 2) 9.50 11.50 11.90 13.90 16.70
MCA(Minimum Circuit Amps)
A
31.30 40.00 48.90 52.50 52.50
MFA/MOP(Maximum Fuse Amps) 40.00 40.00 50.00 75.00 75.00
COP
Nominal Cooling 1)
W/W
4.49 4.09 3.91 3.69 3.55
Nominal Heating 2) 4.74 4.35 4.76 4.53 4.15
ESEER 7.02 6.78 6.59 6.56 6.25
Compressor
Type - INV x 1 INV x 2 INV x 2 INV x 2 INV x 2
Output kW 5.8 4.7 x 2 5.8 x 2 5.8 x 2 5.8 x 2
Model Name - DS-GB066FA**** DS-GB052FA**** DS-GB066FA**** DS-GB066FA**** DS-GB066FA****
Oil
Type - FVC68D FVC68D FVC68D FVC68D FVC68D
Initial Charge cc 3900 6200 6200 6200 6200
Fan
Type - Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC
Output x n W 630 x 2 630 x 2 630 x 2 630 x 2 630 x 2
Air Flow Rate
m³/min 226 250 270 275 280
l/s 3,767 4,167 4,500 4,583 4,667
External Static
Pressure
Max.
mmAq - - - - -
Pa - - - - -
Piping
Connection
Liquid Pipe
Type Braze connection Braze connection Braze connection Braze connection Braze connection
Φ, mm 12.7 12.7 15.88 15.88 15.88
Φ, inch 1/2" 1/2" 5/8" 5/8" 5/8"
Gas Pipe
Type Braze connection Braze connection Braze connection Braze connection Braze connection
Φ, mm 28.58 28.58 28.58 28.58 28.58
Φ, inch 1+1/8" 1+1/8" 1+1/8" 1+1/8" 1+1/8"
Discharge Gas Pipe
Φ, mm 19.05 22.22 22.22 28.58 28.58
Φ, inch 3/4" 7/8" 7/8" 1+1/8" 1+1/8"
Piping length
ODU-IDU Max. m 200(220) 200(220) 200(220) 200(220) 200(220)
After branch Max. m 90 90 90 90 90
Total piping length System Actual m 1000 1000 1000 1000 1000
Level difference
ODU-IDU
Outdoor unit in high-
est position
m 110 110 110 110 110
Indoor unit in high-
est position
m 110 110 110 110 110
IDU-IDU Max. m 50 50 50 50 50
Refrigerant
Type - R410A R410A R410A R410A R410A
Factory Charging kg 7.7 7.4 8.7 8.4 8.4
Sound
Sound Pressure
Cooling
dB(A)
- - - - -
Heating - - - - -
Sound Power - - - - -
External
Dimension
Net Weight
DVMS HP
kg
235 278 300 300 300
DVMS HR 214 184 306 306 306
Shipping Weight
DVMS HP
kg
254 297 319 319 319
DVMS HR 260 303 325 325 325
Net Dimension (WxHxD) mm 1295x1695x765 1295x1695x765 1295x1695x765 1295x1695x765 1295x1695x765
Shipping Dimension (WxHxD) mm 1363x1857x832 1363x1857x832 1363x1857x832 1363x1857x832 1363x1857x832
Operating
Temp. Range
Cooling
DVMS HP
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
DVMS HR -15.0 ~ 48.0 -15.0 ~ 48.0 -15.0 ~ 48.0 -15.0 ~ 48.0 -15.0 ~ 48.0
Heating
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
2-5-1 Outdoor Unit (cont.)
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.