Samsung Electronics 52
Product Specifications
Image
Model Name AM140JXVAFH/AZ AM160JXVAFH/AZ AM180JXVAFH/AZ AM200JXVAFH/AZ
Power Supply Φ, V, Hz 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP
Performance
HP HP 14 16 18 20
Capacity
(Nominal)
Cooling
kW 40.0 45.0 50.4 56.0
Btu/h 136,500 153,500 172,000 191,100
Heating
kW 45 50.4 56.7 63
Btu/h 153,500 172,000 193,500 215,000
Power
Power Input
(Nominal)
Cooling 1) kW 8.47 10.64 10.66 11.45
Heating 2) 9.18 10.30 10.40 12.70
Current Input
(Nominal)
Cooling 1) A 24.70 31.00 31.10 33.40
Heating 2) 26.80 30.00 30.30 37.00
Running
Current
Cooling A 24.70 31.00 31.10 33.40
Heating 26.80 30.00 30.30 37.00
Max 50.00 56.10 66.50 73.00
Power
Consumption
Cooling kW 8.47 10.64 10.66 11.45
Heating 9.18 10.30 10.40 12.70
MCA(Minimum Circuit Amps) A 55.00 62.00 73.00 80.00
MFA/MOP(Maximum Fuse Amps) A 75.00 75.00 75.00 90.00
COP
Nominal Cooling 1) W/W 4.720 4.230 4.730 4.890
Nominal Heating 2) 4.900 4.890 5.450 4.960
ESEER - - - -
Compressor
Type - Scroll Inverter Scroll Inverter Scroll Inverter Scroll Inverter
Output kW 5.18 x 2 5.18 x 2 6.45 x 2 6.45 x 2
Model Name -
DS-GB052FBVASG x 2 DS-GB052FBVASG x 2 DS4GJ5066EVASG x 2 DS4GJ5066EVASG x 2
Oil
Type - PVE PVE PVE PVE
Initial Charge cc - - - -
Fan
Type - Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC
Output x n W 620 x 2 620 x 2 620 x 2 620 x 2
Air Flow Rate
m³/min 255 255 260 265
l/s 4250 4250 4333 4417
External Static
Pressure
Max.
mmAq 8 8 8 8
Pa 78.45 78.45 78.45 78.45
Piping
Connection
Liquid Pipe
Type Braze connection Braze connection Braze connection Braze connection
Φ, mm 12.7 12.7 15.88 15.88
Φ, inch 1/2" 1/2" 5/8" 5/8"
Gas Pipe
Type Braze connection Braze connection Braze connection Braze connection
Φ, mm 28.58 28.58 28.58 28.58
Φ, inch 1+1/8" 1+1/8" 1+1/8" 1+1/8"
High pressure gas pipe
Φ, mm - - - -
Φ, inch - - - -
Piping length
ODU-IDU Max. m 200(220) 200(220) 200(220) 200(220)
After branch Max. m 90 90 90 90
Total piping
length
System Actual m 1000 1000 1000 1000
Level
difference
ODU-IDU
Outdoor unit in
highest position
m 110 110 110 110
Indoor unit in
highest position
m 110 110 110 110
IDU-IDU Max. m 50 50 50 50
Refrigerant
Type - R410A R410A R410A R410A
Factory Charging kg 7.7 7.7 8.4 8.4
Sound
Sound Pressure
Cooling
dB(A)
61 63 64 65
Heating
Sound Power 81 83 86 87
External
Dimension
Net Weight kg 292 300 300 300
Shipping Weight kg 311 319 319 319
Net Dimension (WxHxD) mm 1295x1695x765 1295x1695x765 1295x1695x765 1295x1695x765
Shipping Dimension (WxHxD) mm 1363x1887x832 1363x1887x832 1363x1887x832 1363x1887x832
Operating
Temp. Range
Cooling
℃
-5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48
Heating
℃
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24
Safety device Item
1 -
High pressure switch
2 -
Fan driver overload protector
3 -
Inverter overload protector
4 -
PC board fuse
2-5-1 Outdoor Unit (cont.)
2-5 Product Specification (cont.)
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.