Samsung Electronics 54
Product Specifications Product Specifications
Samsung Electronics 55
Image
Model Name AM140JXVAJH/AZ AM160JXVAJH/AZ AM180JXVAJH/AZ AM200JXVAJH/AZ AM220JXVAJH/AZ
Power Supply Φ, V, Hz 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP
Performance
HP HP 14 16 18 20 22
Capacity
(Nominal)
Cooling
kW 40.0 45.0 50.4 56.0 61.6
Btu/h 136,500 153,500 172,000 191,100 210,200
Heating
kW 45 50.4 56.7 63 69.3
Btu/h 153,500 172,000 193,500 215,000 236,500
Power
Power Input
(Nominal)
Cooling 1) kW 8.47 10.64 10.66 11.45 15.35
Heating 2) 9.18 10.30 10.40 12.70 15.80
Current Input
(Nominal)
Cooling 1) A 11.80 14.80 14.90 16.00 21.40
Heating 2) 12.80 14.40 14.50 17.70 22.00
Running Current
Cooling A 11.80 14.80 14.90 16.00 21.40
Heating 12.80 14.40 14.50 17.70 22.00
Max 25.00 28.10 33.80 41.80 46.00
Power Consumption
Cooling kW 8.47 10.64 10.66 11.45 15.35
Heating 9.18 10.30 10.40 12.70 15.80
MCA(Minimum Circuit Amps) A 31.00 35.00 42.00 52.00 58.00
MFA/MOP(Maximum Fuse Amps) A 40.00 40.00 50.00 75.00 75.00
COP
Nominal Cooling 1) W/W 4.720 4.230 4.730 4.890 4.010
Nominal Heating 2) 4.900 4.890 5.450 4.960 4.390
ESEER - - - - -
Compressor
Type - Scroll Inverter Scroll Inverter Scroll Inverter Scroll Inverter Scroll Inverter
Output kW 4.39 x 2 4.39 x 2 6.39 x 2 6.39 x 2 6.39 x 2
Model Name - DS-GA046FAVASG x 2 DS-GA046FAVASG x 2 DS-GB066FAVBSG x 2 DS-GB066FAVBSG x 2 DS-GB066FAVBSG x 2
Oil
Type - PVE PVE PVE PVE PVE
Initial Charge cc - - - - -
Fan
Type - Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC
Output x n W 620 x 2 620 x 2 620 x 2 620 x 2 620 x 2
Air Flow Rate
m³/min 255 255 260 265 290
l/s 4250 4250 4333 4417 4833
External Static Pressure Max.
mmAq 8 8 8 8 8
Pa 78.45 78.45 78.45 78.45 78.45
Piping
Connection
Liquid Pipe
Type Braze connection Braze connection Braze connection Braze connection Braze connection
Φ, mm 12.7 12.7 15.88 15.88 15.88
Φ, inch 1/2" 1/2" 5/8" 5/8" 5/8"
Gas Pipe
Type Braze connection Braze connection Braze connection Braze connection Braze connection
Φ, mm 28.58 28.58 28.58 28.58 28.58
Φ, inch 1+1/8" 1+1/8" 1+1/8" 1+1/8" 1+1/8"
High pressure gas pipe
Φ, mm - - - - -
Φ, inch - - - - -
Piping length
ODU-IDU Max. m 200(220) 200(220) 200(220) 200(220) 200(220)
After branch Max. m 90 90 90 90 90
Total piping length System Actual m 1000 1000 1000 1000 1000
Level difference
ODU-IDU
Outdoor unit in highest position m 110 110 110 110 110
Indoor unit in highest position m 110 110 110 110 110
IDU-IDU Max. m 50 50 50 50 50
Wiring
Connections
For power supply
Quantity
ea 5G 5G 5G 5G 5G
For connection with indoor
mm2 0.75~1.50 0.75~1.50 0.75~1.50 0.75~1.50 0.75~1.50
Remark
- F1, F2 F1, F2 F1, F2 F1, F2 F1, F2
Refrigerant
Type - R410A R410A R410A R410A R410A
Factory Charging kg 7.7 7.7 8.4 8.4 8.4
Sound
Sound Pressure
Cooling
dB(A)
61 63 64 65 65
Heating
Sound Power 81 83 86 87 87
External
Dimension
Net Weight kg 283 283 305 305 305
Shipping Weight kg 302 302 324 324 324
Net Dimension (WxHxD) mm 1295x1695x765 1295x1695x765 1295x1695x765 1295x1695x765 1295x1695x765
Shipping Dimension (WxHxD) mm 1363x1887x832 1363x1887x832 1363x1887x832 1363x1887x832 1363x1887x832
Operating
Temp. Range
Cooling
℃
-5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48
Heating
℃
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24
Safety device Item
1 -
High pressure switch
2 -
Fan driver overload protector
3 -
Inverter overload protector
4 -
PC board fuse
2-5-1 Outdoor Unit (cont.)
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2-5 Product Specification (cont.)