Samsung Electronics 72
Product Specifications Product Specifications
Samsung Electronics 73
Image
Model Name AM240KXVAGH/TK AM260KXVAGH/TK AM280KXVAGH/TK AM300KXVAGH/TK
Power Supply Φ, V, Hz 3/AC380-415/50 3/AC380-415/50 3/AC380-415/50 3/AC380-415/50
Mode - HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP
Performance
HP HP 24 26 28 30
Capacity
(Nominal)
Cooling
kW 67.2 72.8 78.6 84.0
Btu/h 229,300 248,400 268,200 28,660
Heating
kW 75.6 81.9 88.2 94.5
Btu/h 258,000 279,500 301,000 322,400
Power
Power Input
(Nominal)
Cooling 1) kW 17.10 18.91 20.68 22.70
Heating 2) 17.42 18.00 20.18 20.59
Current Input
(Nominal)
Cooling 1) A 27.40 30.30 33.20 36.40
Heating 2) 27.90 28.90 32.40 33.00
Running Current
Cooling A 27.40 30.30 33.20 36.40
Heating 27.90 28.90 32.40 33.00
Max 55.00 60.00 67.00 73.00
Power Consumption
Cooling kW 17.10 18.91 20.68 22.70
Heating 17.42 18.00 20.18 20.59
MCA(Minimum Circuit Amps) A 55.00 60.00 67.00 73.00
MFA/MOP(Maximum Fuse Amps) A 63.00 75.00 75.00 80.00
COP
Nominal Cooling 1) W/W 3.930 3.850 3.800 3.700
Nominal Heating 2) 4.340 4.550 4.370 4.590
ESEER - - - -
Compressor
Type - INV x 2EA INV x 2EA INV x 2EA INV x 2EA
Output kW 6.39 x 2 6.39 x 2 6.76 x 2 7.81 x 2
Model Name - DS-GB066FA* DS-GB066FA* DS-GB070FA* DS4G*5080F*
Oil
Type - PVE PVE PVE PVE
Initial Charge cc 1100 x 2 1100 x 2 1100 x 2 1400 x 2
Fan
Type - Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC
Output x n W 620 x 2 620 x 2 620 x 2 620 x 2
Air Flow Rate
/min 340 340 340 340
l/s 5667 5667 5667 5667
External Static Pressure Max.
mmAq 8 8 8 8
Pa 78.45 78.45 78.45 78.45
Piping
Connection
Liquid Pipe
Type Braze connection Braze connection Braze connection Braze connection
Φ, mm 15.88 19.05 19.05 19.05
Φ, inch 5/8" 3/4" 3/4" 3/4"
Gas Pipe
Type Braze connection Braze connection Braze connection Braze connection
Φ, mm 34.92 34.92 34.92 34.92
Φ, inch 1+3/8" 1+3/8" 1+3/8" 1+3/8"
High pressure gas pipe
Φ, mm - - - -
Φ, inch - - - -
Piping length
ODU-IDU Max. m 200(220) 200(220) 200(220) 200(220)
After branch Max. m 90 90 90 90
Total piping length System Actual m 1000 1000 1000 1000
Level difference
ODU-IDU
Outdoor unit in highest
position
m 110 110 110 110
Indoor unit in
highest position
m 110 110 110 110
IDU-IDU Max. m 50 50 50 50
Refrigerant
Type - R410A R410A R410A R410A
Factory Charging kg 12.5 12.5 14 14
Sound
Sound Pressure
Cooling
dB(A)
66 66 69 69
Heating
68 68 71 71
Sound Power 89 89 90 90
External
Dimension
Net Weight kg 333 333 342 350
Shipping Weight kg 355 355 364 372
Net Dimension (WxHxD) mm 1295x1795x765 1295x1795x765 1295x1795x765 1295x1795x765
Shipping Dimension (WxHxD) mm 1363x1987x832 1363x1987x832 1363x1987x832 1363x1987x832
Operating
Temp. Range
Cooling
-5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48
Heating
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24
Safety device Item
1 -
High pressure switch
2 -
Fan driver overload protector
3 -
Inverter overload protector
4 -
PC board fuse
2-5-1 Outdoor Unit (cont.)
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.