EasyManua.ls Logo

Samsung AM080FX A Series - Page 64

Samsung AM080FX A Series
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Specifications
Samsung Electronics 75
Image
Model Name AM300KXVANH/TL AM220KXVJNH/ID AM240KXVJNH/ID
Power Supply Φ, V, Hz 3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
HP HP 30 22 24
Capacity
(Nominal)
Cooling
kW 84.0 61.6 67.2
Btu/h 28,660 210,200 229,300
Heating
kW 94.5 69.3 75.6
Btu/h 322,400 236,500 258,000
Power
Power Input
(Nominal)
Cooling 1)
kW
22.70 15.50 17.10
Heating 2) 20.59 15.80 17.42
Current Input
(Nominal)
Cooling 1)
A
36.40 24.80 27.40
Heating 2) 33.00 25.30 27.90
Running
Current
Cooling
A
36.40 24.80 27.40
Heating 33.00 25.30 27.90
Max 73.00 57.10 63.30
Power
Consumption
Cooling
kW
22.70 15.50 17.10
Heating 20.59 15.80 17.42
MCA(Minimum Circuit Amps) A 73.00 48.00 50.40
MFA/MOP(Maximum Fuse Amps) A 80.00 63.00 63.00
COP
Nominal Cooling 1)
W/W
3.700 3.970 3.930
Nominal Heating 2) 4.590 4.390 4.340
ESEER - - -
Compressor
Type - INV x 2EA INV x 2EA INV x 2EA
Output kW 7.81 x 2 6.39 x 2 6.39 x 2
Model Name - DS4G*5080F* DS-GB066FA* DS-GB066FA*
Oil
Type - PVE PVE PVE
Initial Charge cc 1400 x 2 1100 x 2 1100 x 2
Fan
Type - Propeller + BLDC Propeller + BLDC Propeller + BLDC
Output x n W 620 x 2 620 x 2 620 x 2
Air Flow Rate
/min 340 290 340
l/s 5667 5667 5667
External Static
Pressure
Max.
mmAq 8 8 8
Pa 78.45 78.45 78.45
Piping
Connection
Liquid Pipe
Type Braze connection Braze connection Braze connection
Φ, mm 19.05 15.88 15.88
Φ, inch 3/4" 5/8" 5/8"
Gas Pipe
Type Braze connection Braze connection Braze connection
Φ, mm 34.92 28.58 34.92
Φ, inch 1+3/8" 1+1/8" 1+3/8"
High pressure gas pipe
Φ, mm - - -
Φ, inch - - -
Piping length
ODU-IDU Max. m 200(220) 200(220) 200(220)
After branch Max. m 90 90 90
Total piping
length
System Actual m 1000 1000 1000
Level
difference
ODU-IDU
Outdoor unit in high-
est position
m 110 110 110
Indoor unit in
highest position
m 110 110 110
IDU-IDU Max. m 50 50 50
Refrigerant
Type - R410A R410A R410A
Factory Charging kg 14 10 10
Sound
Sound Pressure
Cooling
dB(A)
69.0 - -
Heating
71.0 - -
Sound Power 90.0 - -
External
Dimension
Net Weight kg 350 330.5 330.5
Shipping Weight kg 372 352.5 352.5
Net Dimension (WxHxD) mm 1295x1795x765 1295x1795x765 1295x1795x765
Shipping Dimension (WxHxD) mm 1363x1987x832 1363x1987x832 1363x1987x832
Operating
Temp. Range
Cooling
-5 ~ 48 -5 ~ 48 -5 ~ 48
Heating
-25 ~ 24 -25 ~ 24 -25 ~ 24
Safety device Item
1 -
High pressure switch
2 -
Fan driver overload protector
3 -
Inverter overload protector
4 -
PC board fuse
2-5-1 Outdoor Unit (cont.)
2-5 Product Specification (cont.)
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.

Table of Contents

Related product manuals