Product Specifications
Samsung Electronics 79
Image
Model Name AM240MXVGNR/TK AM260MXVGNR/TK AM280MXVGNR/TK AM300MXVANR/TK
External
Dimension
Net Weight kg 350.0 358.0 358.0 358.0
Shipping Weight kg 372.0 380.0 380.0 380.0
Net Dimensions (WxHxD)
1,295 x 1,795 x 765 1,295 x 1,795 x 765 1,295 x 1,795 x 765 1,295 x 1,795 x 765
Shipping Dimensions (WxHxD)
1,363 x 1,987 x 832 1,363 x 1,987 x 832 1,363 x 1,987 x 832 1,363 x 1,987 x 832
Operating
Temp. Range
Cooling
-15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48
Heating
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24
Safety device Item
1 - High pressure switch
2 - Fan driver overload protector
3 - Inverter overload protector
4 - PC board fuse
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.

Table of Contents